I-7063AD is intelligently designed to provide signal conditioning system monitoring and safe value settings. I-7063AD is a cost-effective solution for a wide range of valuable industrial control signals and systems. The DCON utility can help users to configure and test I-7063AD Isolated digital input & AC-SSR relay output module. Plenty of library functions and demo programs are provided to let users develop programs easily under Windows, Linux and DOS operating systems. The communication interface is modbus protocol via RS-485. Users may mount the modules on a DIN rail, panel or wall. Modules have a screw-terminal block to connect to the signals.
Specifications
Specifications
- Channels: 8
- Digital Input level:
- Isolated with common power
- Logic level 0: +1V max.
- Logic level 1: +4V to+ 30V
- Isolation voltage: 3750Vrms
- Input impedance: 3KO , 0.5W
- 8 Digital input channel with counter function
- Input Frequency : 100Hz
- 16-bit counter : 0-65,535
- Channels: 3
form "A” relay SPST (N.O.)
- Dry contact
- Characteristics -Contact rating:
    AC:24~ 265Vrms @1.0Arms
    Max. Load current 1.0Arms
    Min. Load current 10mArms
    Max. off-state leakage current
    0.75mA(at 100Vrms 60Hz)
    1.50mA(at 200Vrms 60Hz)
- 1 Cycle surge current : 50A(60Hz)
- Max. on-state voltage drop:1.2Vrms
- Surge strength: 4,000Vac
- Relay on time(Max.): 1ms
- Relay off time(Min.): 1ms+1/2rms
- Insulation resistance: 1,000MOhm min.at 500Vdc
- Life time : long life, maintence free
- RS-485
- Input Power: 10~30Vdc
- Consumption :
    0.7W max. for I-7063A
    1.5W max. for I-7063AD
Digital Input
SSR AC output
Communication Interface
Power Supply