I-7012 is a cost-effective solution for a wide range of valuable industrial control signals and systems. The DCON utility can help users to configure and test I-7012 modules. Plenty of library functions and demo programs are provided to let users develop programs easily under Windows, Linux and DOS operating systems. Users may mount the modules on a DIN rail, panel or wall. Modules have a screw-terminal block to connect to the signals. I-7012D comes with FREE EZ Data Logger Software.
Specifications:
Specifications:
- Analog Input
- Input Channels: 1
- Input Type:
    ±150mV
    ±500mV
    ±1V
    ±5V
    ±10V
   ±20mA (requires optional external 125 ohm resistor)
- Resolution: 16-bit
- Sampling Rate: 10 Samples/ Second
- Accuracy: ±0.05% or better
- Zero Drift: ±20uV/°C
- Span Drift: 25ppm/°C
- Band Width: 5.24Hz
- Common Mode Rejection: 86dB
- Normal Mode Rejection: 100dB
- Photo-Isolation: 3750 Vrms
- Intra-module Isolation, Field to Logic 3000 VDC
- Input Channels: 1
- Digital Input
- Channels: 1
- Logic Level: 0 + 1V max
- Logic Level: 1 + 3.5V to 30V
- Max Input Frequency: 50Hz
- Min.Pulse Width: 1 mS
- Channels: 1
- Digital Output
- Channels 2
- Output Type Sink, Open Collector to 30V
- Output Load 30mA max per channel
- Power dissipation 300 mW
- Channels 2
- Interface
- Interface RS-485
- Format N, 8, 1
- Buad Rate: 1200 ~ 115200bps
- Interface RS-485
- LED Display
- 1 LED Power/ Communication indicator
- I-7012D Versions: 4 1/2 digits
- 1 LED Power/ Communication indicator
- Power
- Input: +10 to +30 Vdc
- Power Consumption: 1.3W (i-7012) / 1.9 W (i-7012D)
- Input: +10 to +30 Vdc
- Environment
- Operating temperature: -25°C to 75°C
- Storage temperature: -40°C to 85°C
- Humidity: 5% to 95%, non-condensing
- Operating temperature: -25°C to 75°C