The I-7011 module provides cost-effective protection and conditioning for a wide range of valuable industrial control signals and systems. DCON utility can help users to configure and test I-7011 modules. Plenty of library functions and demo programs are provided to let users develop programs easily under Windows, Linux and DOS operating systems. Users may mount the modules on a DIN rail, panel or wall. Modules have a screw-terminal block to connect to the signals. I-7011/D/P/PD comes with FREE EZ Data Logger Software.
Specifications
Specifications
- Analog Input
- Type: mV, V , mA (requires optional external 125 ohm resistor)
- Thermocouple: Type J, K, T, E, R, S, B, N, C, L, M
- Input Channel: 1
- Voltage range:
    +/-15mV
    +/-50mV
    +/-100mV
    +/- 500mV
    +/-1V
    +/- 2.5V
- Current range: +/- 20mA
- Resolution: 16-bit
- Sampling rate: 10 Samples/Second
- Bandwidth: 5.24 Hz
- Input impedance: 20M ohms
- Accuracy: ±0.05%
- Zero Drift: ± 0.5uV/ °C
- Span Drift: 25ppm/°C
- CMR @ 50/60 Hz: 150 dB
- NMR @ 50/60 Hz: 100 dB
- Over voltage protection:35V (P-P)
- Isolation: 3000Vrms
- Type: mV, V , mA (requires optional external 125 ohm resistor)
- Digital Input
- Channel: 1
- Logic Level 0: + 1V max
- Logic Level 1: + 3.5V to 30V
- Channel: 1
- Event Counter
- Max Input Frequency: 50Hz
- Min. Pulse Width:1 mS
- Max Input Frequency: 50Hz
- Digital Output
- Channels: 2
- Open collector to 30V
- Output Load: sink 30mA max.
- Power dissipation: 300mW
- Channels: 2
- Display LED
- 4 1/2 digits (for I-7011PD)
- 4 1/2 digits (for I-7011PD)
- Communication Interface
- RS-485
- RS-485
- Power Supply
- Input: +10 to +30 Vdc
- Consumption:
    0.9W for I-7011
    1.5W for I-7011D
Thermocouple type : (C)
Type     Range (°C)
J         -210 ~ +760
K         -270 ~ +1372
T         -270 ~ +400
E         -270 ~ +1000
R         0 ~ +1768
S         0 ~ +1768
B         0 ~ +1820
N         -270 ~ 1300
C         0 ~ 2320
- Input: +10 to +30 Vdc